Highest quality standards are achieved through the implementations of latest technology, decades of experience and everlasting moral values , which have helped us to retain our customers as well as multiply them.
FEATURES | |
• | Microprocessor controlled |
• | Self zero check and calibration check |
• | Digital display of %input, ratio error and phase error |
• | Manual and auto ranging modes |
• | Test 5A and 1A CT with either 1A or 5A reference CT |
• | RS 232C port and parallel port for printing |
• | Built in real time clock |
• | Parameter entry through keyboard |
ELECTRICAL SPECIFICATIONS | ||
• | TYPE | SINGLE PHASE |
• | OPRATING CURRENT | I A / 5A, 0.5VA |
• | AUXILIARY SUPPLY | 110V/240V,AC ±20%, 50/60Hz, 60VA. |
• | ACCURACY | ± 0.5% of reading ±1 % of range |
• | FREQUENCY | 45Hz to 55Hz or 55Hz to 65Hz. |
• | ERROR RANGES | 20% (±19.99% ratio error and (±19.99cR* or 680mins.phase error)) |
2% (±1.999% and (±1.999cR or 68.0 mins.)) | ||
0.2% (±1999ppm and (±1999µR or 6.80 mins.)) | ||
(cR = Centiradians, µR = Microradians, ppm = Parts Per Million). | ||
• | RESOLUTION | 0.05% of range |
• | MEASURING TIME | 7 seconds irrespective of signal level and error range. |
• | OUTPUTS | RS232C port & Parallel port (data in ASCII format). |
• | INSULATION RESISTANCE | Greater than 20 Mohms at 500V. DC. |
• | DIELECTRIC STRENGTH | 2kV RMS for 1 minute |
• | OPERATING TEMP. | 0°C to 55°C |
• | STORAGE TEMP. | -20°C to 70°C |
• | HUMIDITY | Upto 95% RH. |
MECHANICAL SPECIFICATIONS | ||
• | MODEL | CTU |
• | SIZE | 180x320x450mm |
• | WEIGHT (Appro.) | 8.0Kgs |
KEYBOARD CONTROLS | |
0 - 9 | Numeric keys to enter values. |
• | Decimal point. |
ENT | Enter key |
RTC | Enter date and time. |
SR / VA | Enter serial no. and burden. |
Take printout of error readings. | |
SER | Send data to serial port. |
% / ACT | Display input in percentage or actual value. |
DEG/RAD | Display phase error in minutes or centiradians. |
ZERO | Check auto zero. |
CAL | Test self calibration. |
DISPLAYS AND INDICATIONS | |
• | 4 digit LED display each to display input, ratio error and phase error. |
• | LED indications for following quantities |
1) % Input | |
2) Minutes and centiradians. | |
3) Range for 20%, 2%, 0,2% and Auto | |
4) Balance, overrange, zero and calibration. |
PRINTING | |
Date, time, serial no., input (% or actual value), burden, %ratio error, & phase error (minutes or centiradians). |
Ordering information |
1) Type 2) Model 3) Operating current 4)Operating Frequency 5)Auxiliary supply |
* To embrace new technologies and methods. * To give unsurpassed products and services to the clients. * To constantly look for improvement and changes.